Universal 3-beam device for inline measurement of liquids

Measuring sensor OPTISONIC 3000

Process connection EN 1092-1 : DN25...3000; PN10...100

Process connection ASME B16.5 : 1...120"; CL 150...1500

Process temperature : -200...+250°C; -328...+482°F

Ambient temperature (incl. converter) : -40...+65°C; -40...+149°F

Materials Measuring tube, flange : Steel, stainless steel, Hastelloy® C4, duplex

Protection category Measuring sensor : IP65, 67, 68; NEMA4, 4X, 6, 6P

Signal converter UFC 400

Measuring accuracy : Volume flow : DN100; 4": < ± 1.5% of measured value,

      DN150...600; 6...24": < ± 1% of measured value

Process conditions : Liquids with max. 5% solid content and max. 2% gas content

Outputs : Current 4-20 mA, pulse, status

Communication: HART®, PROFIBUS,FF, Modbus®

Power supply : 100...240 VAC; 24 VAC/DC

Protection category : Compact (C) IP67; NEMA6, Field (F) IP65; NEMA4, 4X